IFC Model Health Check: What to Fix Before You Run Compliance Rules
· 4 min read · By Verify AI
Run a model health check before any compliance rule. Rules assume a sound model. If spaces are not bounded, elements are mis-classified or units are wrong, the rules do not just fail, they can return confident wrong answers. Fixing health first means your compliance report shows design issues, not export problems.
Here are seven checks, in the order worth doing them.
1. Bounded spaces
Every occupiable area should be an IfcSpace with a closed boundary. Unbounded spaces break occupant load, travel distance and egress simulations because the path has no valid start or end.
Fix: add walls or room-separation lines where a space is open to another, then re-export.
2. No critical proxies
IfcBuildingElementProxy is a generic placeholder. If a fire exit door or a damper is exported as one, rules for those elements never run.
Fix: map the authoring category to the right IFC class in the export settings. See IFC classification checking.
3. Correct storeys
Every element belongs on the right IfcBuildingStorey. Vertical rules for stairs, shafts and compartmentation depend on it, and MEP elements often arrive without one.
4. Consistent units and scale
A model exported in millimetres and read as metres produces a 1,000x error. A 30 m travel distance can read as 30 mm or 30 km, and every distance and width check is then wrong.
Fix: confirm the project units in the export and in the receiving tool. Spot-check one known dimension, such as a corridor width.
5. Required properties are present
Ratings and flags live in property sets such as Pset_DoorCommon and Pset_WallCommon. If the export option for common property sets is off, those values are not in the file.
Fix: turn on the export of common property sets. In Revit, the IFC export has options for Revit property sets and IFC common property sets.
6. No duplicate or overlapping elements
Overlapping walls or doubled doors lead to false findings, such as two doors counted in one opening.
Fix: remove duplicates in the authoring tool and check for copy-paste errors across linked models.
7. Fire dampers where ducts cross rated walls
This is part model quality and part design: if dampers are not modelled, penetration checks cannot find them. See fire wall continuity and service penetrations.
Health check summary
| Check | What good looks like |
|---|---|
| Spaces | Closed boundaries and a usage on every room |
| Proxies | None on elements rules depend on |
| Storeys | Every element assigned correctly |
| Units | Consistent and spot-checked |
| Properties | Standard property sets exported |
| Duplicates | None |
| Dampers | Modelled at rated crossings |
Revit export reminders
- File > Export > IFC. Choose IFC2x3 Coordination View 2.0 or IFC4 Reference View.
- Property Sets: tick "Export Revit property sets" and "Export IFC common property sets".
- Spatial elements: tick "Export rooms in 3D views" so room boundaries are generated.
- Advanced: store the IFC GUID in an element parameter after export.
Frequently asked questions
What is an IFC model health check?
A test of the quality of an IFC file, separate from code compliance: whether spaces are bounded, elements classified, storeys correct, units consistent and properties present.
Why does health come before compliance?
Because compliance rules rely on a sound model. A health problem produces unreliable results.
Which IFC versions can be checked?
IFC2x3 and IFC4, including coordinated models exported from Revit.
How often should I run it?
On every model update that goes to a check, so problems are fixed while they are small.
Run a health check on your model
Verify AI reports model health findings first, then runs fire and MEP rules. See the model health check page, download the IFC validation matrix, or talk to the founder.
Sources
General information. Confirm export options for your authoring tool and IFC version.